UPS Battery Sizing Calculator

Calculate battery quantity, configuration, cut-off voltage and discharge current.

INPUTS

System Parameters

Final battery selection should be verified against the manufacturer's discharge curves and project requirements.
OUTPUTS

Calculation Results

Total System Load 120.00 kW
DC System Voltage 384 V
Backup Duration 15 min
Cut-off Voltage 10.02 V
Cell Voltage 1.67 V
Batteries Per String 32 Pcs/String
Parallel Strings Required 1 String
Recommended Configuration 32S 1P
Total Batteries Required 32 Units
Discharge Current / Battery 486.6 A
BATTERY CONFIGURATION

Battery Connection Diagram

Series and parallel connection of the recommended battery bank.

32S 1P
+ DC OUTPUT
STRING 1
12V
12V
12V
12V
12V
12V
...
32 Batteries / String × 1 String = 32 Batteries Total
DC OUTPUT